2 of the 3 phases on my PAN-42 are showing reflected/mirrored power factors. How is that possible?

Written by Omri Landman

Updated at April 30th, 2025

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Using the Platform
    Getting Started Administration Energy Applications Triggers and Notification Center Data Export Data Import Reports
  • Hardware & Deployment
    Frequently Asked Questions (FAQ) Hardware Datasheets and Deployment Guides Software Deployment Guide Troubleshooting Flow Charts
  • Interactive Demos
  • Legal
+ More

If the phases are not aligned in the installation, the power factor data lines will look like they are reflections of each other (mirror).

To fix this, confirm the right phases are installed in that L1 and I1+/- are matching in their wire position and so on for the remaining phases. When looking at the front of a PAN-42, the voltage inputs are installed on the left hand side from top to bottom while the current inputs are installed on the right hand side from bottom to top. 

Download the Installation Quick Guide or the Manual below for more details.

PAN42 Manual.pdf

PAN42 Troubleshooting Checklist.pdf

mirrored phases power factors

Was this article helpful?

Yes
No
Give feedback about this article

Related Articles

  • The power measured on a PAN-42 does not match the power of a PAN-10/PAN-12/PAN-14 of the same device. Why is that?
  • If we have a PAN-42 installed, can we automatically use its measured power factor for subsequent downstream sensors?
  • What are the voltage limitations of the PAN-42 sensors?
Expand