What's New - November 15, 2026

This release brings bidirectional power, THD and Sag & Swell events to PAN-42 sensors, and keeps your alerts correct when hardware moves.

Written by Shir Goldstein

Updated at November 15th, 2026

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Getting Started
  • Dashboard
  • TimeView
    Get started Work with the chart Understand your data Time & comparison Save & share Advanced
  • Energy Apps
  • Alerts & Notifications
  • Reports
  • Administration & Settings
  • Partners
  • Import & Exports
  • Mobile App
    Getting Started & Signing In Navigating the App The Site Dashboard and Its Widgets TimeView Lite Events (Optimize + Event Management) Notifications, alerts & push Preferences, Support & App Behavior
  • Plans & Packages
  • Security & Certification
  • Deployment
  • Hardware Manuals
  • Datasheets & Specs
  • Frequently Asked Questions (FAQ)
    Bridge FAQs PAN-10/PAN-12/PAN-14 Sensors FAQs PAN-42 Sensor FAQs Software Platform FAQs Package FAQs
  • Legal
  • What’s New
  • Bidirectional-Power
  • Energy Star Portfolio Manager
  • Panoramic AI
+ More

Table of Contents

This Week in PowerRadar, in 60 Seconds Bidirectional Power: See Import and Export on PAN-42 Sensors Where You'll See It Good to Know THD: See How Clean Your Power Is How to Turn It On Good to Know Sag & Swell Events: Spot Voltage Dips and Spikes How to Turn It On Good to Know ENERGY STAR: Send Your Monthly Data Automatically How to Get Started Alerts Follow Your Hardware Good to Know Improvements and Fixes Improvements Related Articles

This Week in PowerRadar, in 60 Seconds

Here's a quick look at what's new in PowerRadar this week. In under a minute, see how PAN-42 sensors now show power flowing both ways, how to check your power quality with THD and Sag & Swell events, and what else we've improved. The full details follow below the video.

Your browser does not support HTML5 video.

You can also watch the video on Vimeo.


Bidirectional Power: See Import and Export on PAN-42 Sensors

What changed

PAN-42 sensors can now measure power in both directions. If your site sends energy back to the grid - for example, surplus from solar panels - PowerRadar now shows it. Power you draw from the grid (import) appears above zero. Power you send back (export) appears below zero.

Why it matters

Until now, a negative reading was treated as a wiring problem and hidden. On a site with solar or another on-site source, that meant you only saw half the picture. Now you can see when your site exports, how much, and your net energy - what you imported minus what you exported.

Note: On a bidirectional sensor, a negative value is not an error. It means the site was exporting at that moment.

Where You'll See It

  • TimeView. For Power and Current, the device's line goes below zero while it exports, and the area under zero is shaded. For Energy, each bar shows the net for that interval - a bar below zero means the device exported more than it imported.
  • Real-time power widget. The center of the gauge shows your current net power. When you draw from the grid, the label reads Importing. When you export, the number has a minus sign and the label reads Exporting. The summary panel header changes to Energy summary.
  • Imported, Exported and Net. When the widget is set to Site total, each period (Last 24 hours, Last 7 days, Last 30 days) shows the net value in large type, then Imported (↓) with its change from the previous period, and Exported (↑). Hover over a period to see the full breakdown - Imported (energy drawn from the grid), Exported (energy sent back to the grid), the share of each, and Net (imported minus exported).
  • Export energy counter. In TimeView, click Add-ons and check Export energy counter (Wh), or open a device's Chart series add-ons panel and check it under Overrides. It charts the sensor's own export counter, and works on a single PAN-42 device or circuit.
  • Exports. In Manual Export, choose Export energy counter (kWh). Auto Export jobs for PAN-42 measurements include an exported energy column.

 

Good to Know

  • PAN-42 only. Only PAN-42 sensors can measure export. Each sensor is marked as bidirectional with the Bidirectional toggle in the Deployment Tool, one toggle per phase. If you think a sensor should show export but doesn't, contact your partner or the PowerRadar support team.
  • Other sensors don't change. Sensors that aren't bidirectional work exactly as before.
  • Cost is never negative. Exported energy doesn't turn into a negative cost.
  • Trend arrows hide when they'd mislead. If a period crosses from importing to exporting, a percentage change isn't meaningful, so the widget hides the arrow.
  • Net split is for the whole site. Imported, Exported and Net show only when the widget is set to Site total. For devices, groups or categories, the widget shows the net value.

Read the full article: Bidirectional Power: What to Expect


THD: See How Clean Your Power Is

What changed

You can now add THD (total harmonic distortion) to your TimeView chart. THD shows how far a device's electrical signal is from a clean, smooth wave. There are two separate series: THD - Current and THD - Voltage.

Why it matters

Equipment like variable-speed drives, LED drivers and switching power supplies distort the electrical wave. High distortion can overheat transformers, make motors vibrate and interfere with sensitive equipment. THD helps you spot the problem early and tell whether it comes from your equipment (current) or from the supply (voltage).

How to Turn It On

  1. In TimeView, select a PAN-42 circuit or device. Use a line chart.
  2. Click Add-ons in the toolbar.
  3. Under Quality, check THD - Current, THD - Voltage or both.

To add THD to one device only, hover over its row in the Legend, click the add-ons icon, open Quality and check the same items.

Good to Know

  • Shown as a dashed line on its own right-side axis, in percent. Values above 100% are possible on heavily distorted circuits.
  • Works with any measurement. You can add THD whether the chart shows Power, Current or Voltage.
  • For trends, not compliance. THD - Current is most reliable when distortion is high (above roughly 15-20%). THD - Voltage is indicative and best for spotting trends.
  • Export it too. In Manual Export, choose THD - Current (%) or THD - Voltage (%).

Read the full article: THD (Total Harmonic Distortion)


Sag & Swell Events: Spot Voltage Dips and Spikes

What changed

You can now see voltage sags (short dips) and swells (short spikes) right on your TimeView chart, at the moment they happened.

Why it matters

Sags can make equipment trip or malfunction. Swells can damage sensitive electronics. Now you can line up an equipment problem with a real voltage event, on the same chart, instead of guessing.

How to Turn It On

  1. In TimeView, select a PAN-42 circuit or device and set the measurement to Voltage.
  2. Hover over the device's row in the Legend and click the add-ons icon.
  3. Open Quality and check Sag & Swell events.

Each event shows as a shaded band - red for a sag, blue for a swell - with a short label giving the total duration and count. Hover over it to see the event type, the affected phase, the count and how long it lasted.

Good to Know

  • Voltage only. Sag & Swell events appear only when the chart shows Voltage, for date ranges of up to one year.
  • Compare. Events show in Split view, but not while Compare is overlaid.
  • No event means nothing happened - not that data is missing. Very short or shallow dips may not be captured.
  • Export it too. In Manual Export, choose Sag & Swell events. For Auto Export jobs with PAN-42 measurements, check Include power quality columns to add voltage sag, voltage swell, current THD and voltage THD to each row.

Read the full article: Sag & Swell Events


ENERGY STAR: Send Your Monthly Data Automatically

A reminder

If your sites report to ENERGY STAR Portfolio Manager, PowerRadar can do it for you. Connect a site once, and PowerRadar sends the previous month's electricity consumption to your Portfolio Manager property on the 5th of every month. No more exporting spreadsheets and typing numbers into the EPA's site.

Why it matters

Monthly reporting by hand is slow, and a missed month leaves a gap in your ENERGY STAR data. With the integration on, your data arrives on time every month, and you get an email if a send ever fails.

How to Get Started

  1. Go to Settings and open ENERGY STAR in the left sidebar.
  2. Follow the setup steps. You'll need a Portfolio Manager account and a property for the site. If you already have both, setup takes about ten minutes.

Once connected, the ENERGY STAR page shows your score, the last and next sync, and the sync history.

Read the full article: Send your energy data to ENERGY STAR automatically


Alerts Follow Your Hardware

What changed

Alerts now stay correct when a bridge, device or meter is moved to another site or customer, returned to inventory, or deleted. PowerRadar removes the hardware from every alert that watches it - at site and account level alike.

Why it matters

Until now, an alert kept watching hardware even after it left your site. In some cases this sent alerts about equipment you no longer own, or kept an alert running with nothing real behind it. Now each alert only watches hardware that still belongs to its site or account.

Good to Know

  • An alert with nothing left to watch is switched off. It stays in your list as an inactive draft, so you can add new hardware and switch it back on.
  • Reinstalled hardware isn't added back automatically. If a bridge is installed again, add it back to the alerts that should cover it.
  • Saving checks the bridges. When you save or switch on a bridge alert, PowerRadar keeps only the bridges that belong to its account. If none are left, you'll see "Select at least one bridge before activating this trigger".
  • Existing alerts were cleaned up. As part of this release, we removed hardware that had already left its site or account from existing alerts. A small number of alerts with nothing left to watch were switched off. You'll see the change on the alert itself.

Improvements and Fixes

Improvements

  • Dashboard totals match TimeView. The energy totals for Last 24 hours, Last 7 days and Last 30 days in the Real-time power widget now use the same periods as TimeView, so both screens show the same numbers.
  • Real-time widgets load faster. The Real-time power and Real-time meters & sensors widgets now make fewer requests, so they load faster on busy dashboards.

Related Articles

  • Bidirectional Power: What to Expect 
  • Bidirectional Power in TimeView
  • Real-Time Power Widget
  • Real-time Power Widget & Dashboards
  • Exporting Bidirectional Data (Manual & Auto Export)
  • Enabling Bidirectional Power (Deployment Tool)
  • Send your energy data to ENERGY STAR automatically
  • THD (Total Harmonic Distortion)
  • Sag & Swell Events
  • Chart Series Add-ons & PAN-42 Metrics
what's new bidirectional updates import export net solar generation thd total harmonic distortion pan-42 sag swell sag and swell power quality energy star

Was this article helpful?

Yes
No
Give feedback about this article

Related Articles

  • Panoramic AI: TimeView Assistant Overview
Expand