Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Contact Us
Italian
US English (US)
ES Spanish
IT Italian
  • Home
  • Hardware e distribuzione
  • Schede tecniche hardware e guide di distribuzione
  • Guide e schede tecniche su hardware e sicurezza
  • Manuals

Manuale PAN-10 e PAN-12

Written by Zarin Keydar

Updated at August 8th, 2025

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Utilizzo della piattaforma
    Rapporti Applicazioni energetiche Trigger e Centro notifiche Iniziare Esportazione dati Importazione dati Amministrazione
  • Hardware e distribuzione
    Diagrammi di flusso per la risoluzione dei problemi Guida alla distribuzione del software Schede tecniche hardware e guide di distribuzione Domande frequenti (FAQ)
  • Demo interattive
  • Legal
+ More

Per scaricarlo in formato PDF, clicca qui

Dichiarazione di conformità FCC

Questo dispositivo è stato testato e ritenuto conforme ai limiti previsti per i dispositivi digitali di Classe B, ai sensi della Parte 15 delle Norme FCC. Tali limiti sono concepiti per fornire una protezione ragionevole contro interferenze dannose nelle installazioni residenziali. Questa apparecchiatura genera, utilizza e può irradiare energia a radiofrequenza e, se non installata e utilizzata in conformità alle istruzioni, può causare interferenze dannose alla ricezione radiotelevisiva.

Tuttavia, non vi è alcuna garanzia che non si verifichino interferenze in una particolare installazione. Se questo dispositivo causa tali interferenze, verificabili spegnendolo e riaccendendolo, si consiglia all'utente di eliminarle adottando una o più delle seguenti misure:

  • Riorientare o riposizionare l'antenna ricevente.
  • Aumentare la distanza tra il dispositivo e il ricevitore.
  • Collegare il dispositivo a una presa di corrente su un circuito diverso da quello che fornisce alimentazione al ricevitore.
  • Rivolgersi al rivenditore o a un tecnico radio/TV esperto.

Avvertenza: modifiche o alterazioni apportate a questa unità non espressamente approvate dalla parte responsabile della conformità potrebbero invalidare l' autorità dell'utente a utilizzare l'apparecchiatura.

Questo dispositivo è conforme alla Parte 15 delle Norme FCC. Il funzionamento è soggetto a
due condizioni:

  1. Questo dispositivo non può causare interferenze dannose e
  2. Questo dispositivo deve accettare qualsiasi interferenza che potrebbe essere ricevuta o che potrebbe causare un funzionamento indesiderato.

Esposizione RF

Questo dispositivo è stato testato per la conformità ai limiti di esposizione alle radiofrequenze FCC in configurazione portatile. È necessario mantenere sempre una distanza di almeno 20 cm tra il dispositivo PAN-10 / PAN-12 e il corpo dell'utente. Questo dispositivo non deve essere utilizzato con altre antenne o trasmettitori che non siano stati approvati per funzionare in combinazione con questo dispositivo.

Informazioni sul produttore

Panoramic Power Ltd.
Via Atir Yeda 15,
Kfar Saba 4464312, Israele

Telefono: +972-9-7667600

 

Dichiarazione di conformità IC

Questo dispositivo è conforme agli standard RSS esenti da licenza di Innovazione, Scienza e Sviluppo Economico Canada. Il funzionamento è soggetto a due condizioni:

  1. Questo dispositivo non può causare interferenze dannose e
  2. Questo dispositivo deve accettare qualsiasi interferenza che potrebbe essere ricevuta o che potrebbe causare un funzionamento indesiderato.

Durante il funzionamento dell'apparecchiatura, è necessario mantenere una distanza di almeno 10 cm tra l'apparecchiatura e tutte le persone.

Le présent appareil est conforme aux CNR d'Industrie Canada applys aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes:

  1. l'apparecchiatura non deve produrre brouillage, ecc
  2. l'utilizzatore dell'apparecchio deve accettare qualsiasi operazione radioelettrica subi, anche se il funzionamento è suscettibile di compromettere il funzionamento.

Una distanza di almeno 10 cm tra l'apparecchiatura e tutte le persone deve essere mantenuta durante il funzionamento dell'apparecchiatura.

 

Gestione della fine dell'uso del prodotto (RAEE) -
Rifiuti di apparecchiature elettriche ed elettroniche

Panoramic Power si impegna a proteggere l'ambiente globale e ad aiutare i propri clienti a riciclare i propri prodotti. Lo smaltimento dei prodotti elettrici ed elettronici deve essere effettuato in conformità con le normative locali e nazionali. È possibile restituire il prodotto presso un punto di raccolta locale.

Per informazioni sui punti di smaltimento o di raccolta, chiama il tuo distributore o venditore oppure contatta https://www.powerradar.energy/support .

 

Precauzioni di sicurezza – Installazione Sensor di potenza Panoramic

Icona  Descrizione generata automaticamente L'installazione di questo prodotto (il "sensore") deve essere effettuata da personale qualificato e competente in ambito elettrico per prevenire pericoli, lesioni o decessi dovuti ai rischi significativi associati al lavoro su o in prossimità di conduttori elettrici sotto tensione. È necessario seguire un sistema di lavoro elettrico sicuro (SSoW)/condizioni di lavoro elettrico sicuro per prevenire qualsiasi potenziale incidente, che includa un'adeguata e sufficiente valutazione dei rischi. La valutazione dei rischi deve riguardare il lavoro su o in prossimità dell'apparecchiatura elettrica specifica e deve essere eseguita da una persona con una conoscenza approfondita ed esperienza di questo tipo di lavoro e dei mezzi per controllare i rischi.

L'alimentazione elettrica al quadro di distribuzione dove avviene l'installazione deve essere isolato (spento seguendo le procedure/linee guida di blocco/etichettatura appropriate) prima e durante l'installazione del/i sensore/i.

Forma, freccia  Descrizione generata automaticamente Laddove ritenuto accettabile e in conformità con tutte le leggi, le norme o i regolamenti internazionali, federali, statali e locali applicabili e vigenti (ad esempio NFPA 70E) e con qualsiasi altra autorità competente, per l'installazione da eseguire su un conduttore sotto tensione (filo sotto tensione), per motivi di sicurezza e rischio di scosse elettriche involontarie, devono essere dettagliati nel SSoW controlli aggiuntivi adeguati. Ciò include, ma non si limita a: l'uso di utensili, attrezzature e indumenti protettivi isolati e verificati (Commissione Elettrotecnica Internazionale - IEC), inclusi guanti isolati elettricamente e resistenti all'arco elettrico.

Un'immagine contenente testo, guanti, forchetta  Descrizione generata automaticamente Negli impianti elettrici obsoleti, quando si rimuovono barriere/coperture dagli involucri elettrici, è necessario tenere in considerazione la possibilità di parti elettriche esposte (ad esempio, senza materiale isolante) all'interno dell'apparecchiatura di distribuzione o qualsiasi deterioramento dell'isolamento su singoli conduttori isolati all'interno, dove è necessaria un'interazione intrusiva per installare il sensore.

Forma  Descrizione generata automaticamente con bassa affidabilità Il sensore deve essere installato solo su un conduttore isolato e non deve essere installato vicino o a contatto con altri conduttori elettrici esposti non isolati, poiché la vicinanza a conduttori elettrici non isolati potrebbe causare un cortocircuito elettrico (arco elettrico).

Icona  Descrizione generata automaticamente Il sensore deve essere compatibile con le dimensioni fisiche e la corrente di carico elettrico massimo del conduttore e in conformità con le linee guida delle specifiche di installazione che devono essere rispettate in modo completo; ciò include informazioni quali l'orientamento del sensore in relazione al carico elettrico, installato in aree non pericolose (ad esempio atmosfere esplosive di polvere, vapore o gas) e entro la temperatura di funzionamento standard del sensore compresa tra 0 e 60 °C (per PAN-1 0)/0 e 50 °C (per PAN-1 2).

Icona  Descrizione generata automaticamente L'installazione è possibile sia sui conduttori di ingresso/uscita esterni prima della morsettiera, sia su entrambe le estremità dell'interruttore. Per l'installazione del sensore, scegliere la posizione più accessibile all'interno dell'armadio elettrico, al fine di ridurre al minimo il rischio di pericoli e lesioni. Il sensore deve essere installato in modo che la freccia punti nella direzione del carico. Panoramic Power non si assume alcuna responsabilità per l'errato montaggio del dispositivo .

Panoramica

Il Panoramic Power System monitora il consumo di energia elettrica a livello di singolo circuito e rileva l'eccesso di utilizzo, consentendo alle organizzazioni di identificare e ridurre le spese energetiche e di manutenzione. 

Il Panoramic Power System è costituito da sensori wireless autoalimentati, progettati per consentire un'installazione rapida e non invasiva, con un impatto minimo sul funzionamento. Sensor si collegano facilmente agli interruttori automatici semplicemente agganciandoli al cavo elettrico in uscita. Monitorano il flusso di elettricità attraverso il campo magnetico risultante e lo utilizzano anche come fonte di alimentazione. I sensori non richiedono alcuna manutenzione. 

I dati raccolti dai sensori vengono inviati a un Bridge , che a sua volta trasferisce le informazioni al server del Panoramic Power System tramite Internet, utilizzando la tecnologia Cloud. 

I sensori segnalano il consumo energetico al Bridge a intervalli inferiori al minuto. I report sui consumi possono essere consultati tramite il sistema. 

Questa guida per l'utente spiega come installare i sensori. 

Flusso di lavoro

L'installazione Sensor consiste nei seguenti passaggi:

  1. Mappare i circuiti.
  2. Collegare fisicamente i sensori ai fili.
  3. Monitora il corretto funzionamento dei sensori.

Questo manuale illustra i passaggi 1 e 2 del flusso di lavoro. Per il passaggio 3, consulta il nostro articolo qui sotto:

Distribuzione Web - Introduzione

Panoramica

Il sistema di gestione energetica di Panoramic Power è la piattaforma leader di intelligence energetica a livello di dispositivo. La piattaforma software monitora il consumo di energia elettrica a livello di singolo circuito e rileva eventuali consumi eccessivi. La nostra tecnologia brevettata di sensori è abbinata ad analisi basate su cloud per fornire informazioni utili per una gestione energetica ottimizzata. Ciò consente alle organizzazioni di identificare e ridurre le spese energetiche e di manutenzione e di migliorare le prestazioni a livello di sistema.

In questa guida spiegheremo come utilizzare lo strumento di distribuzione Web, che ti consentirà di mappare rapidamente siti di grandi dimensioni e completare l'installazione dei sensori per i tuoi progetti.

Sensor di potenza Panoramic

Il segreto del sistema Panoramic Power risiede nei nostri esclusivi sensori wireless e non invasivi. Questi sensori consentono alle organizzazioni di un'ampia gamma di settori di raccogliere in modo rapido e semplice dati sui consumi energetici in tempo reale su tutti i carichi critici di ogni struttura, senza interrompere l'attività aziendale in corso.

I sensori wireless autoalimentati sono progettati per un'installazione rapida e non invasiva, con un impatto minimo sul funzionamento. Sensor si collegano facilmente agli interruttori automatici semplicemente agganciandoli a un filo elettrico in uscita. I sensori monitorano il flusso di elettricità attraverso il campo magnetico risultante e lo utilizzano anche come fonte di alimentazione. Non richiedono alcuna manutenzione.

I dati raccolti dai sensori vengono inviati a un Bridge , che a sua volta trasferisce le informazioni al server tramite Internet, utilizzando la tecnologia cloud. I sensori segnalano il consumo energetico al Bridge a intervalli inferiori al minuto. Report dettagliati sui consumi possono quindi essere recuperati tramite il sistema.

L'installazione Sensor è composta dai seguenti passaggi, illustrati in dettaglio in questa guida.

  • Mappatura dei dispositivi e dei circuiti di un sito.
  • Installazione fisica dei sensori sui cavi elettrici.
  • Monitoraggio del corretto funzionamento dei sensori.

Accesso allo strumento di distribuzione Web

Lo strumento di distribuzione web sarà disponibile per qualsiasi utente con l'autorizzazione "Utente Deployer" . Con questa autorizzazione, potrai aprire un sito e visualizzare la scheda "Strumento di distribuzione" una volta entrato nel sito.

Gerarchia di distribuzione

Per iniziare a mappare il tuo account, dovrai impostare la gerarchia corretta, come segue.

  • Conti
  • Siti
  • Bridge s
  • Zone
  • Pannelli
  • Dispositivi
  • Circuiti
  • Sensor s

Per maggiori dettagli, consulta il nostro articolo sulla gerarchia elettrica.

Nota: è necessario esaminare l'intera gerarchia sopra indicata, anche se un sito è costituito da una sola zona e tutti i pannelli sono concentrati in quella zona.

Gerarchia e viste di distribuzione

La navigazione nella scheda Strumento di distribuzione avviene tramite l'albero sul lato sinistro dello schermo. La gerarchia è la seguente: Siti > Zone > Pannelli > Dispositivi.

  • Facendo clic sul livello Sito nell'albero verrà visualizzato l'elenco Zone sulla destra.
  • Facendo clic sul livello Zona verrà visualizzato l'elenco dei Pannelli sulla destra.
  • Facendo clic sul livello Pannello verrà visualizzato l'elenco Dispositivi sulla destra.

Ripartizione della gerarchia di distribuzione

La gerarchia di distribuzione è la seguente:

  • Account – Al vertice della gerarchia si trova l'account del cliente. Gli account potrebbero essere, ad esempio, un produttore industriale con più stabilimenti in sedi distinte o una grande catena di negozi composta da più sedi. I clienti sono predefiniti nel nostro strumento web. Gli utenti con accesso a più clienti inizieranno selezionandone uno. L'implementazione stessa creerà le gerarchie al di sotto di ciascun cliente. Si noti che gli account (o un elenco di sedi) verranno visualizzati solo per gli utenti con determinate autorizzazioni.
  • Siti – I clienti hanno siti. Le nostre applicazioni software integrate controllano e gestiscono il processo di installazione di più endpoint su più siti. Lo strumento di distribuzione Web può essere utilizzato non solo per installare nuovi siti, ma anche per modificare o aggiungere elementi a un sito esistente.
  • Zone – Ogni sito è suddiviso gerarchicamente in zone (ad esempio, ala ovest, piano di produzione).
  • Quadri elettrici – I quadri elettrici possono alimentare i dispositivi di una singola zona. I quadri elettrici forniscono energia a un sottoinsieme di dispositivi nel sito. Suddividono l'alimentazione elettrica in circuiti sussidiari, fornendo al contempo un interruttore di protezione per ciascun circuito in armadi comuni.
  • Dispositivi : ogni pannello fornisce energia a un insieme di dispositivi, ovvero gli elementi che consumano energia nel tuo sito, macchinari, HVAC, ecc.
  • Circuiti – A seconda del tipo di collegamento del pannello, i dispositivi sono alimentati da una fase, da due o tre fasi. I circuiti rappresentano queste fasi.
  • Sensor - Su ciascuno dei circuiti verranno installati Sensor per misurare con precisione la potenza del dispositivo.
  • Bridge – Bridge collegano i sensori di un pannello o di un gruppo di pannelli fisicamente vicini al servizio cloud. È necessario installare almeno un bridge presso la propria sede; in genere, un bridge copre tutti i dispositivi di un determinato pannello o di una determinata zona.

Nota: è necessario esaminare l'intera gerarchia sopra indicata, anche se un sito è costituito da una sola zona e tutti i pannelli sono concentrati in quella zona.

Mappatura dei circuiti del sito

Creazione di un sito

Il primo passo per mappare i tuoi circuiti è creare un nuovo sito. Puoi anche accedere a un sito esistente che hai già creato.

Per creare un sito, nella parte inferiore della schermata iniziale della Dashboard dell'account , fai clic su + Crea sito .

Quindi segui i passaggi descritti nell'articolo Impostazioni sito per creare un nuovo sito.

Impostazioni del sito

Come utente amministratore o distributore, puoi modificare qualsiasi sito all'interno di qualsiasi account nel tuo ambito. Dalla dashboard del sito, puoi cliccare su Impostazioni dal menu di navigazione a sinistra.

Nelle Impostazioni puoi visualizzare e modificare le Impostazioni generali , le Tariffe dei servizi e l'Importazione dati operativi .

È possibile impostare il nome del sito, l'indirizzo, il tipo di struttura, la sottocategoria, l'area (utilizzata nell'applicazione Benchmarking ), il fuso orario, la pianificazione, il fattore di carbonio e abilitare la categoria Generazione per i dispositivi.

Nota: il fuso orario deve essere impostato in base all'ora solare (anche durante l'ora legale). Il sistema si adatta all'ora legale, ma questa impostazione non viene visualizzata nel menu a tendina.

Pianificazione e Fattore di Carbonio sono impostazioni che si applicano solo alle funzionalità del pacchetto Optimize. Il Fattore di Carbonio si applica alla vista Emissioni di Carbonio nella Nuova Visualizzazione Temporale e al widget Impronta di Carbonio nelle Dashboard .

Dovresti selezionare una pianificazione per il tuo sito, per definirne gli orari di apertura/chiusura. La pianificazione degli orari di apertura e chiusura del sito è efficace per i report relativi agli orari di chiusura e per i trigger che tengono conto degli orari di apertura e chiusura di un sito.

Nota: le pianificazioni stesse vengono create nelle impostazioni dell'account

Se monitori le risorse di generazione sul tuo sito, ad esempio fotovoltaico/solare, dovresti contrassegnare il tuo sito come se supportasse la generazione .

Tariffe dei servizi pubblici

Puoi quindi scegliere una tariffa che definisca i costi per kWh di produzione nel tuo sito.

Dopo aver definito le tariffe per l'account (dalle impostazioni dell'account), puoi selezionare i piani tariffari per i diversi punti vendita del tuo account. Puoi farlo nella scheda Tariffe Servizi nelle Impostazioni del Punto Vendita.

Per ogni tipo di servizio, assegnare uno dei piani tariffari impostati a livello di account. La tariffa di generazione è abilitata solo se la generazione è abilitata per il sito (nella scheda Proprietà sito) e può essere la stessa della tariffa di consumo o impostata come tariffa diversa.

Importazione dati operativi

La funzionalità di importazione dati operativi consente di importare sulla piattaforma tutti i dati relativi alle operazioni.

Per saperne di più, leggi il nostro articolo Importazione dati operativi qui sotto:

Importazione dati operativi

La funzionalità di importazione dati operativi consente di importare sulla piattaforma tutti i dati relativi alle operazioni.

Il formato di importazione supportato è un file CSV.

Il formato CSV

marca temporale tipo_relazione id_relazione valore unità unità_desc
data + ora sito / gruppo_dispositivi / dispositivo sito/gruppo di dispositivi/ID dispositivo valore numerico unità di visualizzazione nome della parte / descrizione dell'unità
2022-06-01 21:59:00 gruppo_dispositivi 12345 16 Tonnellata viti

  • timestamp - data e ora in cui i dati sono stati misurati, in uno dei seguenti formati:
    • %Y-%m-%d %H:%M:%S (formato ISO 8601)
      Esempio: 2022-04-17 11:25:12
    • %m/%d/%Y %H:%M:%S
      Esempio: 17/04/2022 11:25:12
    • %d %b %Y %H:%M:%S
      Esempio: 17 aprile 2022 11:25:12
    • %Y %b %d %H:%M:%S
      Esempio: 17 aprile 2022 11:25:12
    • %d/%b/%Y:%H:%M:%S
      Esempio: 17/Apr/2022:11:25:12
  • relationship_type - l'entità nel software a cui sono correlati i dati in questa specifica riga.
    È possibile correlare i dati a un sito, a un dispositivo specifico o a un gruppo di dispositivi.
    Le voci valide in questo tipo di cella sono:
    • sito
    • dispositivo
    • gruppo_dispositivi
  • relationship_id - ID del sito/dispositivo/gruppo di dispositivi.
    Puoi trovare i tuoi ID nel menu di supporto "Visualizza ID di siti, dispositivi e gruppi di dispositivi" (mostrato nella prima immagine)
  • valore - qualsiasi valore numerico che descrive il valore di ciò che è stato misurato
  • unità : le unità in cui viene misurato questo valore.
    Esempio: Kg, Tonnellate, Pezzi, Scatole, Litri, ecc.
    Poiché si tratta di un inserimento di testo libero, puoi aggiungere qualsiasi unità
    La lunghezza dell'unità è limitata a 30 caratteri.
  • unit_desc - una descrizione specifica per l'unità selezionata
    Esempio: chiodi, viti, piatti, acqua
    La lunghezza della descrizione dell'unità è limitata a 50 caratteri.

Importa CSV manualmente

È possibile importare manualmente il CSV nel software.

Sulla piattaforma Panoramic Power, vai alle Impostazioni sito del sito a cui vuoi che siano correlati i dati.

Nelle impostazioni del sito, vai alla scheda Importazione dati Ops.

In quella scheda, fai clic su " Importa manualmente "

Trascina il file CSV nel posto designato e clicca su "Invia".

Il file verrà sottoposto a un processo di convalida del formato.

In caso di problemi di convalida del formato verrà visualizzata un'indicazione di errore.

Come faccio a sapere se i miei dati sono stati archiviati correttamente?

Dopo un'importazione dati riuscita, la data dell'ultima importazione verrà aggiornata.

Puoi vedere la data dell'ultima importazione nella sezione Importazione dati operazioni nelle impostazioni del sito.

In quali casi questa funzionalità potrebbe essere utile?

Puoi utilizzare la funzionalità di importazione dei dati operativi per praticamente qualsiasi tipo di dati esterni che desideri importare nella piattaforma.

Alcuni esempi sono:

- Dati di produzione

- Bilancio

- Dati operativi

Come posso accedere ai dati?

Attualmente, i dati sono archiviati nel database della piattaforma e possono essere utilizzati per generare report personalizzati avanzati.

Nel prossimo futuro prevediamo di estendere questa funzionalità e di visualizzare i dati Ops. direttamente sulla piattaforma.


È quindi possibile accedere allo strumento di distribuzione per iniziare a mappare i siti e distribuire Sensor sui siti dalla dashboard del sito nella scheda Configurazione nel menu di navigazione.

Aggiungere una zona

Una volta entrato nel tuo sito (dopo averne creato uno), potrai visualizzare un elenco di zone al suo interno. Puoi cliccare su "Crea nuova zona" nell'angolo destro dello schermo per creare una nuova zona, oppure cliccare su una zona esistente per visualizzarne le proprietà.

Specificare un nome e l' area della zona se si desidera utilizzarla come fattore di normalizzazione nell'applicazione di benchmarking . In caso contrario, questa caratteristica è facoltativa.

Web Deployment - Setting Bridge s, Loggers, & Pulse Connected Meters

Setting Bridges, Loggers & Pulse Connected Meters

This article details how to set Bridges, Loggers and External Meters that connect to the platform via a pulse input.

Bridges feature [2] independent KY pulse inputs channels.

To get started, the Bridge must be assigned to a site. The configuration is done in the Inventory section of a Site Dashboard.

Adding a Bridge or Logger

During the mapping stage, you will also need to add a Bridge that connect different groups of sensors to the network. Typically you will set up a Bridge per panel, or a couple of panels in the same zone.

We recommend first installing the Bridge creating the connection to the cloud. This way, once you’ve installed the sensors you’ll immediately get signals for the reception validation.

To add a new Bridge navigate to the site's Bridges & Loggers inventory table from the Site's navigation menu.

To create a new Bridge or Logger, click + Add New and select either "Bridge" or "Logger"

It is recommended to Name the Bridge based on its physical location or the panel(s) in which it is closest to. Description is a free text field that can be shown in a column on the Bridge Status window for additional details of the Bridge. Serial Number is above the barcode on the Bridge on the front (lower right corner) and the back towards the bottom.

Notes: 

  • Once Panels are created, you can go back and Edit Bridges and associate the Panels to specific Bridges. This does not affect Bridge/Sensor operation - this is purely for awareness purposes.
  • To remove a bridge, click Uninstall Bridge in the Edit Bridge Properties screen. 
 

For Loggers, give any Name you wish. Select Obvius as the Logger Type. Provide a Password. Provide the Serial Number (S/N) of the Logger. Click Apply when finished.

Adding a non-Electric External Meter

In order to set a pulse connected meter that isn't Electric type and associate it to a 4th generation bridge or a 3rd party logger, go to the External Meters tab under the Inventory section on the navigation menu of a site and click on +Add New

Fill in the meter's parameters:

  • Meter Name: assign a descriptive name for the meter (what it measures)
  • Meter S/N: is the S/N the meter itself, it is for record only and can help identify the physical meter connected to the Bridge.
  • Meter Type: select from the supported options. Supported types are: Gas, Water, Heat and Compressed Air meters.
  • Associated Bridge/Logger: Choose the Bridge/logger the meter is connected to from the list of supported Bridges and loggers set up in the site.
  • Scaling Factor: set the ratio between pulses and the measured unit. For electricity, for example, it will be kWh per pulse.
    Important: use KYZ scaling factor (rather than KY scaling factor) when connecting electricity meters even though only two wires are connected to the Bridge. When connecting other types of meters, use the KY scaling factor. KY scaling factor is exactly twice that of KYZ.

Note: Different type of meters may require additional parameters.

 

The parameters below are relevant for Gas meters only:

  • Normalization: Volume changes with temperature and pressure, therefore these parameters are relevant for flow meters such as Gas that are not Normalized.

Normal cubic meter (Nm3) - Volume in Temperature: 0 °C, Pressure: 1.01325 barA
Standard cubic meter (Sm3) - Volume in Temperature: 20 °C, Pressure: 1.01325 barA

Depending on the meters selected units type. If units are already normalized (Nm3, Sm3 or SCF), the first field in the Normalization (Normalization Factor) will be disabled. However, if you select a unit that is not normalized, you can enter the Normalization parameters to see normalized volume units.

  • Calorific Factor: Calorific Factor is a measure of heating power and is dependent upon the composition of the gas meters (only). The Calorific Factor refers to the amount of energy released when a known volume of gas is completely combusted under specified conditions. The CF of gas, which is dry, gross and measured at standard conditions of temperature (15 °C) and pressure (1013.25 millibars), is usually quoted in mega-joules per cubic meter (MJ/m3). 

Channel: the physical channel on the Bridge/logger the pulse is connected to

Note: "Disconnected" option in the "Associated Bridge/logger" allows to define a meter before the Bridge/logger is installed. It also allows to disassociate the meter from the logger in case a Bridge/logger needs replacement

 

You can edit or delete an existing meter by clicking the three dots on the of the requested meter

Later on, we will discuss how to configure an Electricity Meter in the Add Devices section of this article.

Verifying Data Flowing from the Bridge

The settings detailed above can be done before or after the physical installation of the Bridge; however, you can only verify the data after post-Bridge installation.

  1. First, verify that the Bridge is connected to the platform.
    • Go to the Bridges inventory view by either clicking on the Bridges & Loggers view in the Inventory widget
  • Make sure that the Bridge is connected. A green status icon indicates that it is.
  • You can also click on the Bridge name and the Connected Sensors table will populate below and in the Last Measurement column will display the last time the Sensors within its range reported to it.

Note: The sensors are delivering the data for any Bridge within its range to collect and deliver to the server. The server will then take the one with the strongest RSSI to report its sensor's data in the system. So there is no need to be worried about multiple Bridges reading the same sensors; there will not be interference or duplicates in the data readings in the system.

 

 

  1. From the Site Dashboard navigation menu, click the Time View application.
  2. Clicking on the Measurement Type show by will present all existing meters in the site. All external meters will be presented under one of the following: 
    • Gas
    • Heat
    • Air
    • Water

The daily view presents aggregated five minutes data. The Gen4 measurement resolution of electricity meters is every one minute. Use the 6 Hours view to see the data in one-minute resolution.

Sites with Gas, Heat, Flow and Temperature Meters

Gas and Heat measurement is presented in energy, and the resolution is every one hour.

Gas, Water and Compressed Air measurement are presented in flow or Volume units (cubic meter, cubic feet and Gallon), for volume measurements the resolution is every one hour and for flow measurements the resolution changes based on the period selected in the graph, illustrated in the second image. Temperature meter measurements are presented as degrees, Celsius or Fahrenheit.

Validating Heat, Gas Water, Compressed Air, and Temperature Readings

After the meters are configurated on the platform, we start the validation process to make sure the readings on the platform are the same as on the physical meter onsite.

For four hours on every round hour, take physical counter readings and pictures from all meters onsite. Compare the delta between hours of those readings to the energy view in the Time View energy graph (the view will be updated after the whole hour has passed; at the end of the measurement period, the energy of 01:00 am will be updated only at 02:01 am).

For example:

Hour  Physical Meter Counter (kwh)   Physical Meter Counter (kwh)   UI Energy in Time View (kwh)  % 
07-01-2018 00:00  113000 200 kwh 200 kwh 100%
07-01-2018 01:00  113200 230 kwh 230 kwh 100%
07-01-2018 02:00  113430   70 kwh 70 kwh 100%
07-01-2018 03:00  113500   0 kwh 0 kwh 100%
07-01-2018 04:00  113500 0 kwh 0 kwh 100%

 

 

 

 

 

 

 

This is a validated meter.

Note: the fixed difference between the UI and the physical meter might be caused by a difference in

1) the Scaling factor and

2) the Caloric factor

 

 

 

Precauzioni di sicurezza

  • Il sensore deve essere installato solo su un conduttore isolato. 
  • Il diametro del conduttore e la corrente massima devono corrispondere alle specifiche stampate sul sensore. 
  • Il sensore deve essere installato e rimosso solo da un elettricista qualificato.
  • Per motivi di sicurezza e per evitare rischi di scosse elettriche, l'installazione non deve essere eseguita su cavi sotto tensione. L'alimentazione del pannello deve essere interrotta prima e durante l'installazione. 
  • Il sensore non deve essere installato in posizione orizzontale o a contatto con barre collettrici o altri conduttori esposti non isolati. 
  • L'installazione è possibile sia sui conduttori di entrata/uscita esterni prima
    la morsettiera, così come entrambe le estremità dell'interruttore. Per l'installazione, scegliere la posizione meno angusta e più accessibile.

Descrizione dell'hardware

Questa procedura deve essere eseguita solo da un elettricista certificato. Sono supportati i seguenti sensori:

  • 63A, coperchio a scatto.
  • 225A, coperchio a clip.

I sensori vengono spediti chiusi, per proteggere il nucleo da polvere e altri agenti inquinanti. Aprire il sensore solo al momento dell'installazione.

Figura 1. 63A Figura 2. 225A

Il sensore è dotato di un'etichetta fissata su di esso, contenente un ID univoco. Il codice a barre sotto l'ID è scansionabile e restituirà l'ID univoco del sensore. Si prega di annotare questo ID poiché è necessario nella fase di configurazione effettuata tramite lo strumento di distribuzione sulla piattaforma o lo strumento di configurazione Bridge per le implementazioni Modbus.

Mappatura del sito 

Sensor vengono installati nel quadro elettrico della rete elettrica e/o dei dispositivi che si desidera monitorare. Per ogni zona o pannello, è necessario installare un Bridge entro il raggio d'azione per raccogliere i dati dei sensori. Visita il nostro Knowledge Base Center per saperne di più su come installare i Bridge e mappare i sensori.

Un triangolo bianco e nero con un punto esclamativo  Il contenuto generato dall'intelligenza artificiale potrebbe essere errato. Installazione di un sensore

Questo processo si divide in due fasi:

  1. Collegamento fisico dei sensori ai fili del circuito.
  2. Registrazione dell'installazione nella piattaforma software Panoramic Power.

Collegamento dei sensori ai circuiti

Per installare un sensore, seguire questi passaggi:

  1. Aprire il coperchio del quadro elettrico.
  2. Assicuratevi di avere un piano che indichi i circuiti da monitorare e gli ID dei sensori associati a ciascuno di essi. Identificate l'interruttore automatico su cui desiderate installare il sensore.

L'ID appare sull'etichetta fissata al sensore.

Per i Sensor PAN-10:

  1. Scegli un sensore e fai scorrere l'apriporta in posizione dal lato etichettato verso il coperchio.
  2. Inserire i perni dell'apriporta nei quattro fori
    Collegamenti/Screen%20Shot%202018-01-31%20at%2011.31.13.png

Figura 4. Far scorrere l'apriporta in posizione

  1. Premere i due lati dell'apriporta per rilasciare il coperchio del sensore.

Una persona che tiene in mano un oggetto arancione  Il contenuto generato dall'intelligenza artificiale potrebbe essere errato.

Figura 5. Premere l'apriporta per rilasciare il coperchio.

Per i Sensor PAN-12

  1. Sollevare la clip per aprire il sensore usando le mani o un cacciavite

  1. Assicurarsi che le quattro superfici principali siano prive di polvere o altre particelle. Se necessario, pulirle con un panno asciutto.

Nota: se possibile, evitare di installare il sensore dietro i cavi e posizionarlo nella parte anteriore del pannello .

  1. Posizionare l'apertura del sensore su una sezione pulita del cavo elettrico, in modo che l'ID del sensore e il codice a barre siano visibili e facilmente leggibili.
  2. Chiudere il coperchio del sensore, facendolo scattare in posizione e assicurandosi che i magneti si colleghino all'interno e che il sensore sia ben chiuso.

Registrazione del sensore installato

Consulta l'articolo seguente sulla mappatura dei sensori sui dispositivi configurati sul sito:

Distribuzione Web - Pannelli di mappatura, dispositivi e circuiti

Aggiunta di un quadro elettrico

  1. Per aggiungere un nuovo pannello (a una zona esistente) o modificarne le impostazioni, accedi alla zona che desideri visualizzare nella scheda Strumento di distribuzione . Da lì puoi visualizzare un elenco dei pannelli esistenti in quella zona o crearne uno nuovo.
  1. Quando crei un nuovo pannello, puoi aggiungere un nome e selezionare la zona per quel pannello.
  2. Selezionare quindi un Tipo di Connessione . Il tipo di connessione descrive la configurazione elettrica del pannello, che spesso dipende dal tipo di servizio di rete in ingresso nel sito. I tipi di connessione disponibili dipendono dalla posizione geografica. Ad esempio, i tipi di connessione per il Nord America sono diversi da quelli per il resto del mondo. Le opzioni disponibili dipendono dalla posizione geografica del sito e dal tipo di pannello selezionato. La Tabella 1 di seguito elenca le opzioni per il Nord America, mentre la Tabella 2 di seguito elenca le opzioni per il resto del mondo.
    Selezionando un tipo di connessione , verrà visualizzata a destra un'immagine di anteprima della configurazione del pannello selezionato. L'anteprima mostra le tensioni predefinite del pannello e i colori tipici dei cavi previsti nel sito. Tuttavia, potrebbero verificarsi alcune variazioni e si consiglia di verificare i livelli di tensione e i colori prima di definire il pannello.
  3. Nel campo "Tipo di Tensione" , è possibile selezionare una tensione fissa (manuale) per il pannello. Se nel sito è installato almeno un contatore di potenza, anziché un valore di tensione fisso, selezionare "Contatore di Potenza" (questa opzione è disponibile solo se al sito è collegato un contatore Pan-42 ). Se si sceglie un contatore di potenza, la tensione utilizzata per il calcolo della potenza di tutti i dispositivi del pannello si baserà sulla tensione misurata, anziché su un valore fisso impostato sul pannello.
  4. Nel campo "Fattore di potenza medio" , specificare il fattore di potenza approssimativo del pannello. Il fattore di potenza è il rapporto tra la potenza effettiva e la potenza apparente dopo il carico. I valori tipici sono compresi tra 0,9 e 1. Il valore predefinito è 0,95. Si noti che la potenza misurata per ciascun dispositivo del pannello viene calcolata come: corrente misurata dal Sensor x tensione del pannello x fattore di potenza.
  5. Al termine, fare clic su Applica .

Opzioni di tipo di connessione del pannello - Nord America

Tipo di pannello

Dispositivo unipolare

Dispositivo a doppio polo

Dispositivo a 3 poli (fase)

Pannello monofase

√

-

-

Pannello bifase

√

√

-

Wye (trifase)

√

√

√

Delta (trifase)

-

-

√

Delta Hi-Leg (trifase)

√

√

√

Pannello di tensione personalizzato (Delta)

-

-

√

Pannello di tensione personalizzato (Wye)

√

√

√

Opzioni di tipo di connessione del pannello - Resto del mondo

Tipo di pannello Dispositivo unipolare Dispositivo a doppio polo Dispositivo a 3 poli (fase)
Pannello monofase √ - -
Wye (trifase) √ √ √

Opzioni di tipo di connessione del pannello - Giappone

Tipo di pannello

Numero di fasi

Tensione di fase predefinita

Tensione predefinita P2P

Famiglia

100 V monofase 2 fili

1

100

Separare

200 V monofase 2 fili

1

200

Separare

100/200V monofase 3 fili

1

100

200

Separare

100/200 V trifase 4 fili (Wye)

3

100

200

WYE

200 V trifase 3 fili (triangolo)

3

100

200

Delta

400 V trifase 3 fili (triangolo)

3

230

400

Delta

Pannello di tensione personalizzato (Delta)

3

Delta

Pannello di tensione personalizzato (Wye)

3

Wye

Aggiungere un dispositivo

Ogni pannello fornisce energia a un insieme di dispositivi, che sono gli elementi che consumano energia nel tuo sito, macchinari, HVAC, ecc.

  • Per aggiungere un nuovo dispositivo (a un pannello esistente) o modificarne le impostazioni, accedi al pannello esistente. Da lì, puoi visualizzare un elenco dei dispositivi esistenti in quel pannello o crearne uno nuovo.

Nota: puoi fare clic sulla piccola freccia a sinistra di un dispositivo esistente per espanderlo e visualizzare ulteriori dettagli e informazioni su quel dispositivo

  • Inserisci un Nome , una Categoria e un Tipo per il tuo dispositivo. Nel campo Tipo , utilizza una tipologia che descriva i principali consumatori di elettricità per questo dispositivo, ad esempio Macchinari, Illuminazione, Riscaldamento industriale, ecc.

Categoria personalizzata e tipo personalizzato

  • Per i siti Optimize, puoi creare categorie e tipi personalizzati per i tuoi dispositivi. Ogni entità personalizzata richiede un nome e un'icona che puoi selezionare dalla nostra libreria.

Nota: ogni categoria personalizzata richiede almeno 1 tipo personalizzato configurato.

Nota: è possibile aggiungere tipi personalizzati all'interno delle categorie esistenti nel sistema.

  • Nel menu a discesa "Monitorato da ", seleziona se il dispositivo è monitorato da un Sensor Panoramic o da un misuratore di impulsi elettrici esterno. Quando selezioni il misuratore di impulsi elettrici, alcuni campi potrebbero essere modificati di conseguenza.
  • Nel campo "Numero di fasi/circuiti" , seleziona la combinazione di fasi e sensori che desideri implementare. In base al tipo di connessione del pannello, i dispositivi sono alimentati da una singola fase, oppure da due o tre fasi. Per un dispositivo monofase, è possibile installare un singolo sensore. Per un dispositivo bifase o trifase, puoi scegliere se installare un sensore per ciascuna fase o acquisire le misurazioni da una sola fase. Successivamente, quando viene calcolata la potenza complessiva del dispositivo, puoi sommare la corrente di tutti i sensori oppure, se è installato un solo sensore, moltiplicare la misurazione per il fattore di corrente. I sensori PAN-42 richiedono una configurazione trifase/3 Sensor . Una volta installato il sensore sulla prima fase, le fasi rimanenti compileranno automaticamente i dettagli PAN-42 come la potenza del trasformatore di corrente e il fattore di corrente.
  • Nel campo Corrente dell'interruttore automatico , immettere la corrente nominale massima dell'interruttore (Ampere) per cui è progettato il circuito.
  • Utilizzare il campo Note per aggiungere eventuali note o commenti aggiuntivi riguardanti questo dispositivo.
  • Al termine, fare clic su Applica .

Note:

  • Una volta creato un nuovo dispositivo, nell'elenco dei dispositivi è possibile collegare i sensori/misuratori al dispositivo specifico.
  • Fai clic su "Espandi tutto" in cima all'elenco dei dispositivi per espandere i dettagli di tutti i dispositivi. Fai clic su "Modalità di modifica" per modificare singolarmente ogni componente del dispositivo.

Assegnazione di un Sensor Panoramic a un dispositivo

  • Una volta inserito il numero di serie, potrai visualizzare ulteriori dettagli sul sensore. Il sistema determinerà automaticamente di che tipo di sensore si tratta in base al numero di serie.
  • Il fattore di potenza è un valore compreso tra 0 e 1 che rappresenta la qualità/efficienza della potenza effettiva. L'account è impostato di default, ma se si conosce il fattore di potenza misurato o presunto di ciascun dispositivo, è possibile inserirlo qui. Inserire questo valore solo per i dispositivi misurati PAN-10, PAN-12 e PAN-14, poiché i sensori PAN-42 misurano questo valore.
  • Il fattore di corrente rappresenta i casi in cui è necessario compensare nel sistema l'installazione del sensore su 1 solo degli X conduttori per fase. Ad esempio: se un dispositivo ha 4 conduttori per fase e si potesse inserire solo 1 dei 4 conduttori nel sensore, si dovrebbe inserire il valore 4 nel fattore di corrente e quindi il sistema moltiplicherebbe tutte le letture di corrente per 4 per rappresentare il valore reale della fase. Questo è consigliato solo se il carico su tutti e 4 i conduttori è bilanciato. Per garantire letture accurate del sensore, è ideale dimensionare il sensore o il trasformatore di corrente (TA) per i casi PAN-14 in modo che sia sufficientemente grande da alloggiare tutti i conduttori nello stesso sensore e, pertanto, il fattore di corrente dovrebbe essere impostato su 1.

Per sensori PAN-42

  • Il Fattore di Tensione è impostato su 1 per impostazione predefinita, ma nei casi in cui sia installato un trasformatore di potenziale per ridurre una tensione superiore al valore nominale del PAN-42 (480 V), questo campo consente di compensarne la presenza. Ad esempio: se fosse presente un trasformatore di potenziale che riduce la tensione da 4800 V a 480 V, si dovrebbe inserire il valore 10 nel campo Fattore di Tensione.
  • Per i misuratori di potenza PAN-14 Sensor e PAN-42, sarà necessario inserire la corrente di uscita del trasformatore di corrente (CT Rate) . Si tratta del valore di corrente primario delle specifiche del trasmettitore di corrente esterno. Ad esempio: per un trasformatore di corrente da 600 A/5 A, inserire il valore 600 nella corrente di uscita del trasformatore di corrente (CT Rate) .
  • Una volta installato, quando il dispositivo è in funzione e un Bridge nelle vicinanze è online, è anche possibile visualizzare un'anteprima in tempo reale del grafico di convalida Sensor , con dettagli sulla velocità di ricezione e sulla corrente del sensore selezionato.

Nota: se si desidera rimuovere o sostituire fisicamente un sensore dal circuito, selezionare "Disinstalla Sensor sulla destra. I dati storici verranno mantenuti finché il dispositivo non verrà eliminato . I dati dei sensori disinstallati possono essere visualizzati nella vista Energia e Tempo facendo clic con il pulsante destro del mouse sul nome del sito e selezionando " Mostra dispositivi disinstallati ".

Assegnazione di un misuratore di impulsi elettrici a un dispositivo

  • Dopo aver espanso le proprietà del dispositivo / o aver cliccato su Connetti contatore , potrai impostare:
    • Bridge /Logger associato : seleziona un Bridge Panoramic o un logger Obvius esterno
    • L' ingresso del canale a cui è collegato il sotto-contatore del dispositivo nel Bridge /logger
    • Il fattore di scala (energia (kWh) per impulso)
  • Fare clic su Connetti per completare la configurazione

Divisione/Eliminazione di dispositivi, pannelli e zone

Quando si visualizza l'elenco dei dispositivi in un pannello, l'elenco dei pannelli in una zona o l'elenco delle zone in un sito, è possibile scegliere di duplicare o dividere un dispositivo, un pannello o una zona.

  1. Per dividere un dispositivo, vai a destra dell'elenco dei dispositivi e seleziona " Dividi dispositivo" . Il dispositivo verrà diviso da un dispositivo, con un paio di sensori installati, a dispositivi singoli con un sensore ciascuno.
  2. Per duplicare o eliminare un dispositivo (con tutti i sensori del dispositivo), segui lo stesso metodo quando sei nel Pannello schermata che visualizza l'elenco dei dispositivi.
  3. Per eliminare un pannello (con tutti i dispositivi del pannello), segui lo stesso metodo quando sei nella Zona schermata che visualizza l'elenco dei pannelli.
  4. Per eliminare una zona (con tutti i pannelli e i dispositivi), seguire lo stesso metodo quando ci si trova nella schermata Sito in cui è visualizzato l'elenco delle zone.

Gerarchia elettrica

È possibile modificare e mappare la gerarchia elettrica di un sito facendo clic sul pulsante Gerarchia elettrica nella sezione Configurazione della barra laterale del menu di navigazione della Dashboard del sito.

Viene visualizzata la gerarchia elettrica attuale del sito, da cui è possibile selezionare uno o più dispositivi da spostare sotto un altro dispositivo per stabilire una relazione. Questo vale per i casi in cui viene misurata l'energia in ingresso del pannello principale e dei dispositivi secondari che ne derivano. La definizione di questa gerarchia elettrica sarà importante per il totale del sito; la mancata applicazione di una gerarchia elettrica potrebbe comportare il raddoppio del totale del sito.

Fai clic sull'opzione a 6 punti a sinistra del dispositivo figlio e trascina i dispositivi figlio sul dispositivo padre finché non vedi "interno" sul dispositivo padre, quindi rilascia il mouse per definire la gerarchia elettrica del sito. Una volta stabilita la relazione, ogni dispositivo padre mostrerà accanto al tipo di gerarchia (Consumo o Generazione) il numero di dispositivi figlio a cui è assegnato.

Più livelli si spostano i dispositivi secondari all'interno di un dispositivo principale, più opzioni si espandono nell'opzione con i 3 puntini a destra. Cliccare sull'opzione con i 3 puntini su un dispositivo secondario per spostarlo al livello principale (non gerarchizzato) o per spostarlo a uno o più livelli all'interno della gerarchia.

I dispositivi possono essere spostati nella gerarchia elettrica solo nelle proprietà dei dispositivi come descritto nella tabella seguente.

Da A

Dispositivo trifase

Dispositivo 2 Fase

Dispositivo 1 Fase

Dispositivo di fase di generazione 1

Dispositivo di fase di seconda generazione

Dispositivo di terza fase di generazione

Dispositivo trifase

SÌ

Dispositivo 2 Fase

SÌ

SÌ

Dispositivo 1 Fase

SÌ

SÌ

SÌ

Dispositivo di fase di generazione 1

SÌ

SÌ

SÌ

Dispositivo di fase di seconda generazione

SÌ

SÌ

Dispositivo di terza fase di generazione

SÌ

Nota: se i dispositivi figlio di un dispositivo padre appartengono a una categoria/tipologia diversa dal dispositivo padre, verranno esclusi dalle righe totali Categoria/Tipo dispositivo nella Visualizzazione ora e nella nuova applicazione Visualizzazione ora.

È possibile gerarchizzare i dispositivi di consumo tra altri dispositivi di consumo e i dispositivi di generazione sotto altri dispositivi di generazione. Tuttavia, non è possibile applicare una gerarchia con dispositivi di consumo e dispositivi di generazione contemporaneamente. Pertanto, in cima alla gerarchia, è possibile visualizzare le due gerarchie nelle rispettive schede: Consumo e Tipo di generazione.

È possibile cercare i dispositivi per nome e anche scegliere di ordinare l'elenco dei dispositivi in ordine crescente per Nome, Fase o Riquadro.

Man mano che imposti la gerarchia, un registro delle modifiche verrà visualizzato sulla destra. Fai clic su Salva man mano che apporti le modifiche, ma per annullare le modifiche apportate, fai clic su Reimposta per cancellare le modifiche apportate dall'ultimo salvataggio.

Monitoraggio dell'attività dei sensori

Per saperne di più sulla finestra di riepilogo del sensore che aiuta a monitorare l'attività del sensore, consulta l'articolo seguente:

Bridge e Sensor

Questo articolo riguarda lo stato dell'inventario dei Bridge e dei sensori. Questo include informazioni su se tutti i Bridge di un sito sono connessi e sui livelli di connessione e ricezione di tutti i sensori di un sito.

È possibile accedere a queste pagine di inventario da:

  • Stato hardware dei Sensor e dei Bridge della dashboard dell'account.
  • Le sezioni " Sensor Panoramic " e " Bridge e registratori" nella sezione Inventario della navigazione Account o Sito.

Finestra di riepilogo del Bridge

È possibile utilizzare la scheda Bridge e Logger per visualizzare innanzitutto Bridge e i sensori collegati a ciascun Bridge ; e la scheda Sensor Panoramic per visualizzare tutti i sensori di un sito. Questa scheda può essere aperta anche a livello di account, con una visualizzazione dello stato di tutti Bridge e dei sensori nei siti.


In alto a destra nelle schede Bridge e Sensor , è possibile cercare nell'elenco per sito, per stato Bridge o del sensore, per nome Bridge o del dispositivo o per qualsiasi altra colonna. È possibile visualizzare lo stato della connettività o, per i sensori, la ricezione dei sensori. Una ricezione accettabile è indicata da tre o più barre, una ricezione scarsa è indicata da una o due barre grigie e l'assenza di ricezione è indicata da cinque barre piatte.

Nota: un intervallo accettabile per RSSI è compreso tra -30 dBm e -75 dBm

La visualizzazione dell'inventario dei Bridge e dei Logger può essere effettuata dopo la distribuzione oppure quando si desidera determinare il motivo per cui i dati non vengono visualizzati per i siti sul proprio account.

L'elenco dei Bridge e dei Logger verrà visualizzato in base all'ambito concesso.

Se sei un utente del sito, vedrai solo Bridge del tuo sito; se sei un utente dell'account, vedrai solo i Bridge dei siti del tuo account.
Puoi filtrare l'elenco in base a:

  • Nome Bridge
  • Numero di serie Bridge
  • Nome del sito
  • Nome utente

Finestra di riepilogo del Sensor

Puoi visualizzare l'inventario di tutti i sensori e il loro stato attuale, per scoprire quali sensori funzionano correttamente e quali sono offline. Come per Bridge e logger, puoi utilizzare questa funzionalità dopo l'implementazione o per determinare il motivo per cui i dati non vengono visualizzati per i siti del tuo account.
L'elenco dei sensori verrà visualizzato in base all'ambito concesso.

Se sei un utente del sito, vedrai solo i sensori del tuo sito; se sei un utente dell'account, vedrai solo i sensori dei siti del tuo account.

Puoi filtrare l'elenco in base a:

  • Nome Sensor
  • Nome del circuito - nome del dispositivo + nome del circuito
  • Numero di serie Sensor

Bridge

Domande frequenti Bridge

Domande frequenti Sensor PAN-10/PAN-12/PAN-14

Domande frequenti su PAN-10/PAN-12/PAN-14

Domande frequenti sul Sensor PAN-42

Domande frequenti sul Sensor PAN-42

Domande frequenti sulla piattaforma software

Domande frequenti sulla piattaforma software

 

Disinstallazione di un sensore

Aprire il sensore nello stesso modo in cui lo si è aperto la prima volta e rimuoverlo dal cavo.


Specifiche Sensor

Specifiche

PAN-10 

PAN-12 

Dimensioni fisiche

 

17 x 20 x 32 millimetri

0,67 x 0,79 x 1,26 pollici

46,2 x 22,8 x 32,6 millimetri

1,82 x 0,90 x 1,28 pollici

Diametro esterno massimo dell'aria calda (incluso l'isolamento)

7 millimetri

0,28 pollici

18,8 millimetri

0,74 pollici

Campo di misura attuale

0-63 A

0-225 A

Precisione della misurazione attuale (tipica, a 25° C)

(@ Fattore di cresta <1,5)

<2% a I>3A

 

<2% a I>10A

Corrente minima di esercizio 

0,5 – 1 A

0,7 – 1,2 A

Frequenza CA supportata

 

50 Hz (UE)

60 Hz (USA)

50 Hz (UE)

60 Hz (USA)

Frequenza di trasmissione

 

434 MHz (UE)

902-928 MHz (Stati Uniti)

 

434 MHz (UE)

902-928 MHz (Stati Uniti)

Potenza di trasmissione (ERP)

0 dBm (massimo)

0 dBm (massimo)

Intervallo di trasmissione

10 secondi

10 secondi

Sicurezza e
Certificati EMC

 

Stati Uniti e Canada

Sicurezza: UL-61010-1,
CSA-C22.2

EMC/Radio: FCC Parte 15 sottoparte B, C

Europa

Sicurezza: EN-61010-1 (CE)

EMC: EN-ETSI 301489-3,

Radio: EN-ETSI 300220-1

Stati Uniti e Canada

Sicurezza: UL-61010-1,
CSA-C22.2

EMC/Radio: FCC Parte 15 sottoparte B, C

Europa

Sicurezza: EN-61010-1 (CE)

EMC: EN-ETSI 301489-3,

Radio: EN-ETSI 300220-1

 

Grado di infiammabilità dell'involucro esterno

UL94 V-0

 

UL94 V-0

 

Temperatura di esercizio

-25 - 60° C (-13 - 140 ° F)

-25 - 50° C (-13 – 122 o F)

Intervallo di umidità operativa

5% - 95% senza condensa

5% - 95% senza condensa

Temperatura di conservazione

-25 - 65° C (-13 - 149 o F)

-25 - 65° C (-13 - 149 o F)

 

Gamma di condizioni ambientali nominali

L'unità è destinata all'uso in ambienti interni.

Altitudine fino a 2000 m

CAT III

Grado di inquinamento 2

Risoluzione dei problemi

Se riscontri un problema, prova prima la seguente soluzione:

Problema

Soluzione

Il sensore non invia misurazioni

Assicurarsi che il circuito sia alimentato. 

Assicurarsi che la freccia del sensore punti
nella direzione del carico. 

Assicurarsi che i sensori siano sufficientemente vicini
al ponte per il ponte riceve
i suoi segnali. 

Controllare il LED di ricezione del bridge .
Se non lampeggia significa che è
non riceve segnali. 

Manutenzione e assistenza

Non è richiesta alcuna manutenzione. Per qualsiasi problema, contatta il tuo fornitore di supporto, che potrà inviare un ticket di supporto per tuo conto all'indirizzo: https://www.powerradar.energy/support 

Supporto

È possibile ottenere ulteriore supporto inviando un ticket di supporto a:

https://www.powerradar.energy/support 

Avviso di copyright

Copyright © 2012-2017 Panoramic Power Ltd. Tutti i diritti riservati.

Panoramic Power® è un marchio registrato di Panoramic Power Ltd.
Tutti gli altri marchi commerciali sono di proprietà dei rispettivi titolari.

 

automatizzato potente

Was this article helpful?

Yes
No
Give feedback about this article

Related Articles

  • Manuale Bridge
Expand