PAN-14 Manual
Table of Contents
To download this in a PDF form - click here
FCC compliance statement
This device has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in residential installations. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio and television reception.
However, there is no guarantee that interference will not occur in a particular installation. If this device does cause such interference, which can be verified by turning the device off and on, the user is encouraged to eliminate the interference by one or more of the following measures:
- Re-orient or re-locate the receiving antenna.
- Increase the distance between the device and the receiver.
-
Connect the device to an outlet on a circuit different from the one that
supplies power to the receiver. - Consult the dealer or an experienced radio/TV technician.
Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to
two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference that may be received or that may cause undesired operation.
RF Exposure
This device has been tested for compliance with FCC RF exposure limits in a portable configuration. At least 20 cm of separation distance between the PAN-14 device and the user's body must be maintained at all times. This device must not be used with any other antenna or transmitter that has not been approved to operate in conjunction with this device.
Manufacturer information
Panoramic Power Ltd.
15 Atir Yeda St.,
Kfar Saba 4464312, Israel
Telephone: +972-9-7667600
IC compliance statement
This device complies with Innovation, Science and Economic Development Canada license-exempt RSS standard(s). Operation is subject to two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference that may be received or that may cause undesired operation.
A distance of at least 10 cm between the equipment and all persons should be maintained during the operation of the equipment.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
- l’appareil ne doit pas produire de brouillage, et
- l’utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
Une distance d’au moins 10 cm entre l’équipement et toutes les personnes devraient être maintenues pendant le fonctionnement de l’équipement.
Product end of use handling (WEEE) -
Waste of Electrical and Electronic Equipment
Panoramic Power is committed to protect the global environment and helping our customers with recycle responsibilities. Disposal of electrical and electronic products must be done according with the local and national regulations. You can return your product to a local collection point.
For information about your disposal or collection points, call your distributor or vendor, or contact https://www.powerradar.energy/support .
Safety Precautions – Panoramic Power Sensor Installation
The installation of this product (the ‘sensor’) must be undertaken by an electrically qualified and competent person to prevent danger, injuries or a fatality due to the significant risks associated with work on or near live electrical conductors. An electrical safe system of work (SSoW)/electrical safe work condition must be followed to prevent any potential incident, which shall include a suitable and sufficient risk assessment. The risk assessment shall cover the work on or near the specific electrical equipment and shall be carried out by someone with comprehensive knowledge and experience of this type of work and the means of controlling the risks.
The electrical supply to the distribution panel where the install is taking place must be isolated (shut off following appropriate Lockout/Tagout procedures/guidelines) before and during the installation of the sensor(s).
Where it is determined acceptable, and in compliance with all applicable and current International, Federal, State, and local laws, rules, or regulations (e.g. NFPA 70E) and any other Authorities Having Jurisdiction, for the installation to be performed on an energized conductor (live wire), then for reasons of safety and inadvertent shock hazard suitable additional controls must be detailed within the SSoW. This shall include, but not be limited to; the use of suitably (International Electrotechnical Commission - IEC) verified insulated tools, equipment, protective clothing including electrically insulated gauntlets and Arc Flash resistant.
On aged electrical installations, consideration must be given when removing barriers/covers from electrical enclosures to the potential for exposed electrical parts (i.e. no insulating material) within the distribution equipment or any deterioration of insulation on single insulated conductors within, where intrusive interaction is needed to fit the sensor.
The sensor must be installed only on an insulated conductor and shall not be installed near or touching any other non-insulated exposed electrical conductor as proximity to un-insulated electrical conductors could result in an electrical short circuit (Arc Flash) incident occurring.
The sensor shall be compatible with the physical size and maximum electrical load current of the conductor and in accordance with the installation specification guidance which shall be comprehensively adhered to; this includes such information as sensor orientation in relation to the electrical load, installed in non-hazardous areas (e.g. explosive dust, vapor or gas atmospheres) and within the sensor’s standard operating temperature of between 0 - 60°C
Installation is possible both on external entry/exit conductors before the terminal strip and both ends of the circuit breaker. The most accessible location within the electrical enclosure should be chosen for installation of the sensor in order to minimize the risk of danger and injury. The sensor should be installed so that the arrow points in the direction of the load, panoramic power does not take any responsibility for the incorrect fitting of the device.
Overview
This user guide explains how to install the PAN-14 sensors.

PAN-14 Current sensor

Current Transformer (CT)
Workflow
Sensor installation consists of the following steps:
- Map the circuits.
- Physically attach the sensors and the CTs to the wires.
- Monitor the proper functioning of the sensors.
This manual covers steps 1 and 2 of the workflow. For step 3, visit the article below to learn how:
Web Deployment - Getting Started
Overview
Panoramic Power’s energy management system is the leading device-level energy intelligence platform. The software platform monitors electrical energy consumption at the individual circuit level and detects excess usage. Our patented sensor technology is coupled with cloud-based analytics to provide insights for optimized energy management. This allows organizations to identify and reduce energy and maintenance expenses, and improve their system level performance.
In this guide, we’ll explain how to use the web deployment tool, which will allow you to quickly map large-scale sites and complete your sensor installations for your projects.
Panoramic Power Sensors
The key to the Panoramic Power system is our unique wireless, non-invasive sensors. These sensors enable organizations across a wide range of industries to quickly and easily collect energy consumption data in real time on all critical loads in each facility, without disrupting your current business activity.
The wireless, self-powered sensors are engineered for rapid, non-invasive installation, with almost no disturbance to operations. Sensors are easily attached to circuit breakers by simply snapping them onto an outgoing electrical wire. The sensors monitor the flow of electricity through the resulting magnetic field and also use the field as a power source. They do not require any maintenance.
Data collected by the sensors is sent to a Bridge, which, in turn, transfers the information to the server through the Internet, using cloud technology. The sensors report the energy consumption to the Bridge at sub-minute intervals. Detailed consumption reports can then be retrieved through the system.
Sensor installation consists of the following steps, which are discussed in detail throughout this guide.
- Mapping a site’s devices and circuits.
- Physically installing the sensors to electrical wires.
- Monitoring the proper functioning of the sensors.
Accessing the Web Deployment Tool

The web deployment tool will be available for any user with the Deployer User permission. With this permission, you'll be able to open a site and then view the Deployment Tool tab once entering the site.
Deployment Hierarchy
To start mapping your account, you'll need to set the correct hierarchy, as follows.
- Accounts
- Sites
- Bridges
- Zones
- Panels
- Devices
- Circuits
- Sensors
Please check out our article about Electrical Hierarchy to learn more details.
Deployment Hierarchy and Views
Safety precautions
The sensor must be installed only on an insulated conductor.
CTs output/secondary current must not exceed 5A.
The sensor and CT should be installed and removed only by a qualified electrician.
Installation must not be performed on a live wire for reasons of safety and random shock hazard. Power supply to the panel must be shut off before and during installation.
The sensor and CT must not be installed lying or touching bus bars or any other non-insulated, exposed conductors.
Installation is possible both on external entry/exit conductors before the terminal strip, as well as both ends of the circuit breaker. The least cramped, most accessible location should be chosen for installation. The sensor should be installed such that the arrow points in the direction of the load.
Caution Protection provided by the equipment can be impaired if used in a manner not specified by the manufacturer.
Mapping the site
Sensors are installed at the electrical panel of the mains and/or devices you wish to monitor. Per zone or panel, a Bridge must be installed within range to collect the sensor data. Visit the article below to learn more about how to install Bridges and map sensors:
Web Deployment - Mapping Panels, Devices and Circuits
Adding an Electrical Panel

- To add a new panel (to an existing zone) or edit the settings of an existing panel, go to the zone you want to view within the Deployment Tool tab. From there you can view a list of existing panels within that zone, or create a new panel.

- When you create a new panel, you can add a name and select the zone for that panel.
- Next select a Connection Type. The connection type describes the panel’s electrical configuration, which is most often derived by the type of grid service entering the site. The available connection types are determined by your location. For example, North America connection types differ from the rest of the world. The options available are dependent on the site's location and the panel type selected. Table 1 below lists the device options for North America, and Table 2 below lists the device options for the rest of the world.
When you select a Connection type, a preview image of the selected panel configuration will show to the right. The preview shows the default voltages in the panel as well as the typical colors of the wires expected in the site. Some variations may occur however, and we recommend verifying the voltage levels and colors prior to defining the panel. - In the Voltage Type field, you can select a fixed (manual) voltage for the panel. If at least one power meter is installed on your site, instead of a fixed voltage value, select Power Meter (note that this option is only available if you have a Pan-42 meter connected to the site). If you choose a power meter, the voltage used for power calculation of all the panel’s devices will be based on the measured voltage, instead of a fixed value set on the panel.
- In the Avg. Power factor field, specify the approximate power factor of the panel. The power factor is the ratio of the real power following the load of the apparent power. Typical values here are between 0.9-1. The default value is 0.95. Note that the power measured for each of the panel’s devices is calculated as: Sensor’s measured current x the panel’s voltage x the power factor.
- Click Apply when finished.
Panel Connection Type Options - North America
Panel Type | Single Pole Device |
Dual Pole Device |
3-Pole (phase) Device |
---|---|---|---|
Single Phase Panel | √ |
- |
- |
Dual Phase Panel | √ |
√ |
- |
Wye (3-Phase) | √ |
√ |
√ |
Delta (3-Phase) | - |
- |
√ |
Hi-Leg Delta (3-Phase) | √ |
√ |
√ |
Custom voltage panel (Delta) | - |
- |
√ |
Custom voltage panel (Wye) | √ |
√ |
√ |
Panel Connection Type Options - Rest of the World
Panel Type | Single Pole Device | Dual Pole Device | 3-Pole (phase) Device |
---|---|---|---|
Single Phase Panel | √ | - | - |
Wye (3-Phase) | √ | √ | √ |
Panel Connection Type Options - Japan
Panel Type | Number of Phases |
Phase Default Voltage |
P2P Default Voltage |
Family |
---|---|---|---|---|
100V Single Phase 2 Wire | 1 |
100 |
Single |
|
200V Single Phase 2 Wire | 1 |
200 |
Single |
|
100/200V Single Phase 3 Wire | 1 |
100 |
200 |
Single |
100/200V 3 Phase 4 Wire (Wye) | 3 |
100 |
200 |
WYE |
200V 3 Phase 3 Wire (Delta) | 3 |
100 |
200 |
Delta |
400V 3 Phase 3 Wire (Delta) | 3 |
230 |
400 |
Delta |
Custom Voltage Panel (Delta) | 3 |
Delta |
|
|
Custom Voltage Panel (Wye) | 3 |
Wye |
|
|
Adding a Device

Each panel feeds power to a set of devices, which are the elements that consume power on your site, machinery, HVAC, etc.
- To add a new device (to an existing panel), or edit the settings of an existing device, go into an existing panel. From there, you can view a list of existing devices within that panel, or create a new device.
Note: You can click the small arrow to the left of an existing device, to expand and see additional details and information about that device

- Enter a Name, Category and Type for your device. In the Type field, use a type that describes the main consumers of electricity for this device; for example, Machinery, Lighting, Industrial Heating, etc.
Custom Category and Custom Type
- For Optimize sites, you can create Custom Categories and Custom Types for your devices. Each custom entity requires a name and an icon you can select from our library

Note: Each Custom Category requires at least 1 Custom Type configured with it.
Note: You can add Custom Types within existing Categories in the system.
- In the Monitored By drop-down, select whether the device is monitored by a Panoramic Sensor or by an external Electric Pulse Meter. When selecting Electric Pulse Meter - some fields may adjust accordingly
- In the No. of Phases/Circuits field, select the combination of phases and sensors you’d like to deploy. Based on the connection type of your panel, your devices are fed either with a single phase, or with two or three phases. For a single-phased device, you can install a single sensor. For a two- or three-phased device, you can choose whether you want to install a sensor for each one of the phases, or get measurements from only one phase. Later, when the overall device power is calculated, you can either sum up the current of all sensors, or if one sensor is installed, multiply the measurement by the current factor. PAN-42 sensors require a 3 Phase/3 Sensor setup. Once the sensor is installed on the first phase, the remaining phases will auto-populate the PAN-42 details like CT rating and Current Factor
- In the Circuit Breaker rate field, enter the maximum current breaker rating (Ampers) that the circuit is designed for.
- Use the Notes field to add any additional notes or comments regarding this device.
- Click Apply when finished.
Notes:
- Once you create a new device, in the list of devices, you can connect the sensors/meters to the specific device.
- Click Expand All at the top of the devices list, to expand all of the devices' details. Click Edit Mode to individually edit each device component.
Assigning a Panoramic Sensor to a Device

- Once you enter the serial number there, you'll be able to see additional sensor details. It will automatically determine what type of sensor it is based on its serial number.
- Power Factor is a value between 0 - 1 representing the quality/efficiency of the real power. There is a default set to the account but if you are aware of each device's measured or assumed power factor, enter in this value here. You only enter this value for PAN-10, PAN-12, and PAN-14 measured devices, as PAN-42 sensors will measure this value.
- Current Factor represents cases where you have to compensate in the system for installing the sensor on only 1 of X conductors for a phase. For example: if a device has 4 conductors per phase and you could only fit 1 of the 4 conductors in the sensor, you would put the value 4 in the current factor, and therefore the system would multiply all current readings by 4 to represent the real value of the phase. This is only recommended given the load across all 4 of the conductors is balanced. To ensure accurate sensor readings, it is ideal to size the sensor or the CT for PAN-14 cases to be large enough to fit all conductors into the same sensor and therefore, the Current Factor would be set to 1.
For PAN-42 sensors
- Voltage Factor is set as 1 by default but in cases where you have a potential transformed installed to stepdown a voltage that exceeds the rating of the PAN-42 (480V), this field allows for the compensation of its presence. For example: if there was a potential transformer that stepped down the voltage from 4800V to 480V, you would enter the value 10 in the Voltage Factor field.
- For PAN-14 Sensor and PAN-42 power meters, you will be required to enter the CT Rate. This is the primary current value of the external current transmitter’s specifications. For example: For a 600A/5A CT, enter the value 600 in the CT Rate.
- Once installed and the device is running and a Bridge nearby is online, you can also see a real-time preview of the Sensor Validation Graph, with details of the reception rate and the current of the selected sensor.

Note: If you want to physically remove or replace a sensor from the circuit, select Uninstall Sensor on the right. The historical data will remain as long as the device is not deleted. Uninstalled sensor data can be viewed in the Energy Time View by right clicking on the site name and clicking on "Show Uninstalled Devices".
Assigning an Electric Pulse Meter to a Device

- Once you expand the device properties / or click Connect Meter, you'll be able to set:
- The Associated Bridge/Logger - Select a Panoramic Bridge or external Obvius logger
- The Channel Input to which the device's sub-meter is connected in the Bridge/logger
- The Scaling Factor (energy (kWh) per pulse)
- Click Connect to complete the setup
Splitting/Deleting Devices, Panels, and Zones

When viewing the list of devices in a panel, list of panels in a zone, or list of zones in a site, you can choose to duplicate or split a device, panel, or zone.
- To split a device, go to the right of the list of devices, and select Split Device. The device will be split from one device, with a couple of sensors installed to individual devices with one sensor each.
- To duplicate or delete a device (with all sensors of the device), follow the same method when you are in the Panel screen viewing the list of devices.
- To delete a panel (with all devices of the panel), follow the same method when you are in the Zone screen viewing the list of panels.
- To delete a zone (with all panels and devices), follow the same method when you are in the Site screen viewing the list of zones.
Electrical Hierarchy

You can edit and map a site’s electrical hierarchy by clicking on the Electrical Hierarchy button in the Configuration section of the navigation menu sidebar of the Site Dashboard.
The site's current electrical hierarchy appears, where you can select one or more devices to be moved under another device to establish a relationship. This applies for cases where the incoming main panel energy is measured as well as the children devices feeding off of it. Establishing this Electrical Hierarchy will be important for the site total; not applying an Electrical Hierarchy will result in possibly doubling the site total.


Click on the 6 dot option on the left of the children device and drag and drop the children devices onto their parent until you see “inside” on the parent device and release the mouse to define the site's electrical hierarchy. Once relationship is established, each Parent device will display next to their hierarchy type (Consumption or Generation) the number of children devices it is assigned.

The more levels you move the children device within a parent device, the more options expand on the 3 dot option on the right. Click on the 3 dot option on a Children device to Move it to the Root Level (unhierarchied) or to move to one level or more levels within the hierarchy.
Devices can be moved in the electrical hierarchy only to the devices properties as described in the table below.
ToFrom | Device 3 Phase |
Device 2 Phase |
Device 1 Phase |
Generation 1 Phase Device |
Generation 2 Phase Device |
Generation 3 Phase Device |
---|---|---|---|---|---|---|
Device 3 Phase | YES |
|
|
|
|
|
Device 2 Phase | YES |
YES |
|
|
|
|
Device 1 Phase | YES |
YES |
YES |
|
|
|
Generation 1 Phase Device |
|
|
|
YES |
YES |
YES |
Generation 2 Phase Device |
|
|
|
|
YES |
YES |
Generation 3 Phase Device |
|
|
|
|
|
YES |
Note: If the children devices under a parent device are a different category/type to its parent device, it will be excluded from the Device Category/Type total lines on the Time View and The New Timeview application.


You can hierarchy consumption devices amongst other consumption devices and you can hierarchy generation devices under other generation devices. However, you cannot apply a hierarchy with consumption devices and generation devices together. Therefore at the top of the hierarchy, you can view the two hierarchies in their own tabs: Consumption and Generation type.
You can search the devices by name and also choose to sort the list of devices in ascending Name, Phase or Pane order.

As you set the hierarchy, a Change Log will populate to the right. Click Save as you make the changes but to undo the changes made, click on Reset to wipe the changes made since the previous save.

Installing the sensor
PAN-14 and the associated current transformer should be installed in a location not accessible to an average user. The voltage and current measurement circuit insulation should be adequate for 300V, CAT III, double/reinforced insulation from mains.
This procedure must be carried out by a certified electrician.
-
Connect the PAN-14 sensor to the CT by connecting the two CT’s outputs to the PAN-14 sensor using 1.0-4.0mm2 (12-17 AWG) wires, min. temperature rated 90°C copper wires, as follows:
- Connect the PAN-14 sensor’s terminal marked as ‘1’ to the CT’s terminal marked as ‘S1’ or ‘X1’
- Connect the PAN-14 sensor’s terminal marked as ‘2’ to the CT’s terminal marked as ‘S2’ or ‘X2’
Caution: A loose CT connection can become a fire hazard. When connecting the unit to the CT make sure that both CT wires are properly inserted and that the screws are well tightened.

-
Mount the CT on the hot wire:
-
If the CT is split-core:
Close the CT on the hot wire by disconnecting its two parts and closing them around the hot wire. -
If the CT is solid -core:
Disconnect one of the ends of the hot wire from the panel, insert it through the CT, and then reconnect it to the panel. -
In both cases, make sure the CT is placed on the wire so that the direction of current flow on the wire is from the side marked ‘P1’ or ‘H1’ on the CT, to the side marked ‘P2’ or ‘H2’ on the CT.
Other used CT polarity markings are K for entry and L for exit or Load side (respectively P1 and P2).
-
If the CT is split-core:
- Make sure the sensor’s LED is blinking.

-
Finalize the PAN-14 sensor and the CT’s position on the panel:
- Maintain a reasonable distance between the CT and the sensor.
-
Place the PAN-14 sensor on the side that is closer to the bridge
(to avoid RF blocking, make sure the CT is not positioned between the sensor and the bridge).
Caution: Do not hang the PAN-14 sensor from the CT, as the connection cannot withstand the sensor weight and can become a fire hazard. Make sure that the sensor is properly mounted, for example using plastic ties.
Important notes
- Do not mount the CT on the hot wire before you have already connected the PAN-14 sensor securely to the CT!
- If a PAN-14 sensor needs to be replaced, short circuit the CT’s outputs to each other using a length of wire before PAN-14 is disconnected!
- Do not leave the CT mounted/installed on a hot wire without being short circuited.
- It is possible to have both the PAN-14 sensor and the short-circuiting wire connected to the CT at the same time (but PAN-14 will not measure current accurately while the short-circuiting wire is connected).
Registering the installed sensor
Visit the article below about mapping the sensors to the devices configured to the site:
Web Deployment - Mapping Panels, Devices and Circuits
Adding an Electrical Panel

- To add a new panel (to an existing zone) or edit the settings of an existing panel, go to the zone you want to view within the Deployment Tool tab. From there you can view a list of existing panels within that zone, or create a new panel.

- When you create a new panel, you can add a name and select the zone for that panel.
- Next select a Connection Type. The connection type describes the panel’s electrical configuration, which is most often derived by the type of grid service entering the site. The available connection types are determined by your location. For example, North America connection types differ from the rest of the world. The options available are dependent on the site's location and the panel type selected. Table 1 below lists the device options for North America, and Table 2 below lists the device options for the rest of the world.
When you select a Connection type, a preview image of the selected panel configuration will show to the right. The preview shows the default voltages in the panel as well as the typical colors of the wires expected in the site. Some variations may occur however, and we recommend verifying the voltage levels and colors prior to defining the panel. - In the Voltage Type field, you can select a fixed (manual) voltage for the panel. If at least one power meter is installed on your site, instead of a fixed voltage value, select Power Meter (note that this option is only available if you have a Pan-42 meter connected to the site). If you choose a power meter, the voltage used for power calculation of all the panel’s devices will be based on the measured voltage, instead of a fixed value set on the panel.
- In the Avg. Power factor field, specify the approximate power factor of the panel. The power factor is the ratio of the real power following the load of the apparent power. Typical values here are between 0.9-1. The default value is 0.95. Note that the power measured for each of the panel’s devices is calculated as: Sensor’s measured current x the panel’s voltage x the power factor.
- Click Apply when finished.
Panel Connection Type Options - North America
Panel Type | Single Pole Device |
Dual Pole Device |
3-Pole (phase) Device |
---|---|---|---|
Single Phase Panel | √ |
- |
- |
Dual Phase Panel | √ |
√ |
- |
Wye (3-Phase) | √ |
√ |
√ |
Delta (3-Phase) | - |
- |
√ |
Hi-Leg Delta (3-Phase) | √ |
√ |
√ |
Custom voltage panel (Delta) | - |
- |
√ |
Custom voltage panel (Wye) | √ |
√ |
√ |
Panel Connection Type Options - Rest of the World
Panel Type | Single Pole Device | Dual Pole Device | 3-Pole (phase) Device |
---|---|---|---|
Single Phase Panel | √ | - | - |
Wye (3-Phase) | √ | √ | √ |
Panel Connection Type Options - Japan
Panel Type | Number of Phases |
Phase Default Voltage |
P2P Default Voltage |
Family |
---|---|---|---|---|
100V Single Phase 2 Wire | 1 |
100 |
Single |
|
200V Single Phase 2 Wire | 1 |
200 |
Single |
|
100/200V Single Phase 3 Wire | 1 |
100 |
200 |
Single |
100/200V 3 Phase 4 Wire (Wye) | 3 |
100 |
200 |
WYE |
200V 3 Phase 3 Wire (Delta) | 3 |
100 |
200 |
Delta |
400V 3 Phase 3 Wire (Delta) | 3 |
230 |
400 |
Delta |
Custom Voltage Panel (Delta) | 3 |
Delta |
|
|
Custom Voltage Panel (Wye) | 3 |
Wye |
|
|
Adding a Device

Each panel feeds power to a set of devices, which are the elements that consume power on your site, machinery, HVAC, etc.
- To add a new device (to an existing panel), or edit the settings of an existing device, go into an existing panel. From there, you can view a list of existing devices within that panel, or create a new device.
Note: You can click the small arrow to the left of an existing device, to expand and see additional details and information about that device

- Enter a Name, Category and Type for your device. In the Type field, use a type that describes the main consumers of electricity for this device; for example, Machinery, Lighting, Industrial Heating, etc.
Custom Category and Custom Type
- For Optimize sites, you can create Custom Categories and Custom Types for your devices. Each custom entity requires a name and an icon you can select from our library

Note: Each Custom Category requires at least 1 Custom Type configured with it.
Note: You can add Custom Types within existing Categories in the system.
- In the Monitored By drop-down, select whether the device is monitored by a Panoramic Sensor or by an external Electric Pulse Meter. When selecting Electric Pulse Meter - some fields may adjust accordingly
- In the No. of Phases/Circuits field, select the combination of phases and sensors you’d like to deploy. Based on the connection type of your panel, your devices are fed either with a single phase, or with two or three phases. For a single-phased device, you can install a single sensor. For a two- or three-phased device, you can choose whether you want to install a sensor for each one of the phases, or get measurements from only one phase. Later, when the overall device power is calculated, you can either sum up the current of all sensors, or if one sensor is installed, multiply the measurement by the current factor. PAN-42 sensors require a 3 Phase/3 Sensor setup. Once the sensor is installed on the first phase, the remaining phases will auto-populate the PAN-42 details like CT rating and Current Factor
- In the Circuit Breaker rate field, enter the maximum current breaker rating (Ampers) that the circuit is designed for.
- Use the Notes field to add any additional notes or comments regarding this device.
- Click Apply when finished.
Notes:
- Once you create a new device, in the list of devices, you can connect the sensors/meters to the specific device.
- Click Expand All at the top of the devices list, to expand all of the devices' details. Click Edit Mode to individually edit each device component.
Assigning a Panoramic Sensor to a Device

- Once you enter the serial number there, you'll be able to see additional sensor details. It will automatically determine what type of sensor it is based on its serial number.
- Power Factor is a value between 0 - 1 representing the quality/efficiency of the real power. There is a default set to the account but if you are aware of each device's measured or assumed power factor, enter in this value here. You only enter this value for PAN-10, PAN-12, and PAN-14 measured devices, as PAN-42 sensors will measure this value.
- Current Factor represents cases where you have to compensate in the system for installing the sensor on only 1 of X conductors for a phase. For example: if a device has 4 conductors per phase and you could only fit 1 of the 4 conductors in the sensor, you would put the value 4 in the current factor, and therefore the system would multiply all current readings by 4 to represent the real value of the phase. This is only recommended given the load across all 4 of the conductors is balanced. To ensure accurate sensor readings, it is ideal to size the sensor or the CT for PAN-14 cases to be large enough to fit all conductors into the same sensor and therefore, the Current Factor would be set to 1.
For PAN-42 sensors
- Voltage Factor is set as 1 by default but in cases where you have a potential transformed installed to stepdown a voltage that exceeds the rating of the PAN-42 (480V), this field allows for the compensation of its presence. For example: if there was a potential transformer that stepped down the voltage from 4800V to 480V, you would enter the value 10 in the Voltage Factor field.
- For PAN-14 Sensor and PAN-42 power meters, you will be required to enter the CT Rate. This is the primary current value of the external current transmitter’s specifications. For example: For a 600A/5A CT, enter the value 600 in the CT Rate.
- Once installed and the device is running and a Bridge nearby is online, you can also see a real-time preview of the Sensor Validation Graph, with details of the reception rate and the current of the selected sensor.

Note: If you want to physically remove or replace a sensor from the circuit, select Uninstall Sensor on the right. The historical data will remain as long as the device is not deleted. Uninstalled sensor data can be viewed in the Energy Time View by right clicking on the site name and clicking on "Show Uninstalled Devices".
Assigning an Electric Pulse Meter to a Device

- Once you expand the device properties / or click Connect Meter, you'll be able to set:
- The Associated Bridge/Logger - Select a Panoramic Bridge or external Obvius logger
- The Channel Input to which the device's sub-meter is connected in the Bridge/logger
- The Scaling Factor (energy (kWh) per pulse)
- Click Connect to complete the setup
Splitting/Deleting Devices, Panels, and Zones

When viewing the list of devices in a panel, list of panels in a zone, or list of zones in a site, you can choose to duplicate or split a device, panel, or zone.
- To split a device, go to the right of the list of devices, and select Split Device. The device will be split from one device, with a couple of sensors installed to individual devices with one sensor each.
- To duplicate or delete a device (with all sensors of the device), follow the same method when you are in the Panel screen viewing the list of devices.
- To delete a panel (with all devices of the panel), follow the same method when you are in the Zone screen viewing the list of panels.
- To delete a zone (with all panels and devices), follow the same method when you are in the Site screen viewing the list of zones.
Electrical Hierarchy

You can edit and map a site’s electrical hierarchy by clicking on the Electrical Hierarchy button in the Configuration section of the navigation menu sidebar of the Site Dashboard.
The site's current electrical hierarchy appears, where you can select one or more devices to be moved under another device to establish a relationship. This applies for cases where the incoming main panel energy is measured as well as the children devices feeding off of it. Establishing this Electrical Hierarchy will be important for the site total; not applying an Electrical Hierarchy will result in possibly doubling the site total.


Click on the 6 dot option on the left of the children device and drag and drop the children devices onto their parent until you see “inside” on the parent device and release the mouse to define the site's electrical hierarchy. Once relationship is established, each Parent device will display next to their hierarchy type (Consumption or Generation) the number of children devices it is assigned.

The more levels you move the children device within a parent device, the more options expand on the 3 dot option on the right. Click on the 3 dot option on a Children device to Move it to the Root Level (unhierarchied) or to move to one level or more levels within the hierarchy.
Devices can be moved in the electrical hierarchy only to the devices properties as described in the table below.
ToFrom | Device 3 Phase |
Device 2 Phase |
Device 1 Phase |
Generation 1 Phase Device |
Generation 2 Phase Device |
Generation 3 Phase Device |
---|---|---|---|---|---|---|
Device 3 Phase | YES |
|
|
|
|
|
Device 2 Phase | YES |
YES |
|
|
|
|
Device 1 Phase | YES |
YES |
YES |
|
|
|
Generation 1 Phase Device |
|
|
|
YES |
YES |
YES |
Generation 2 Phase Device |
|
|
|
|
YES |
YES |
Generation 3 Phase Device |
|
|
|
|
|
YES |
Note: If the children devices under a parent device are a different category/type to its parent device, it will be excluded from the Device Category/Type total lines on the Time View and The New Timeview application.


You can hierarchy consumption devices amongst other consumption devices and you can hierarchy generation devices under other generation devices. However, you cannot apply a hierarchy with consumption devices and generation devices together. Therefore at the top of the hierarchy, you can view the two hierarchies in their own tabs: Consumption and Generation type.
You can search the devices by name and also choose to sort the list of devices in ascending Name, Phase or Pane order.

As you set the hierarchy, a Change Log will populate to the right. Click Save as you make the changes but to undo the changes made, click on Reset to wipe the changes made since the previous save.

Monitoring sensor activity
Visit the article below to learn more about the sensor summary window that helps monitor sensor activity:
Bridges and Sensors
This article covers learning about the status of your Bridges and sensors inventory. This includes whether all Bridges at a site are connected, and the connection and reception levels of all sensors at a site.
You can get to these inventory pages from:
- The Account Dashboard Sensors and Bridges Hardware Status.

- The “Panoramic Sensors" and “Bridges & Loggers” sections under the Inventory section of the Account or Site navigation.

Bridges Summary Window
You can use the Bridges & Loggers tab to first view Bridges and sensors connected to each Bridge; and the Panoramic Sensors tab to view all sensors at a site. This can also be opened on the account level, with a view of the status of all Bridges and sensors across sites.

At the top right of the Bridges and Sensors tabs, you can Search the list by site, by Bridge or sensor status, by Bridge or device name, or by any other column. You can see the connectivity status, or - for sensors - the sensors' reception. Reasonable reception is shown as three or more bars, poor reception is indicated by one or two gray bars, and no reception is indicated by five flat bars.
Note: An acceptable range for RSSI is -30dBm thru -75dBm
Viewing the inventory of Bridges and Loggers can be done post-deployment, or when you want to determine why data is not showing up for sites on your account.
The list of Bridges and Loggers will be displayed based on the scope granted.
If you are a site user, you will see only Bridges of your site, and if you are an account user, you will see only Bridges of sites of your account.
You can filter the list based on:
- Bridge name
- Bridge serial number
- Site name
- Account name
Sensors Summary Window
You can view the inventory of all sensors and their current status, to learn which sensors are functioning well, and which are offline. As with Bridges and loggers, you can use this post-deployment, or when trying to determine why data is not showing up for sites on your account.
The list of sensors will be displayed based on the scope granted.
If you are a site user, you will see only sensors of your site, and if you are an account user, you will see only sensors of sites of your account.
You can filter the list based on:
- Sensor name
- Circuit name - device name + circuit name
- Sensor serial number
Bridge FAQs
Bridge Frequently Asked Questions
PAN-10/PAN-12/PAN-14 Sensors FAQs
PAN-10/PAN-12/PAN-14 Frequently Asked Questions
PAN-42 Sensors FAQs
PAN-42 Sensors Frequently Asked Questions
Software Platform FAQs
Uninstalling a sensor
Open the sensor in the way you first opened it and remove it from the cable.
Sensor specifications
Physical dimensions |
33.8 × 29 × 42.5 mm 1.14 × 1.67 inch |
Current input range |
0-5 ARMS (up to 10 A peak) |
Current measurement range |
Any applicable range based on CT ratio |
Current measurement accuracy |
<2% at I > 2% of full-scale current
|
Minimum operating current |
0.03 – 0.05 A
|
AC frequency supported
|
50 Hz (EU) 60 Hz (US) |
Transmission frequency
|
434 MHz (EU) 915 MHz (US) |
Transmission power (ERP) |
0 dBm (max) |
Transmission interval |
10 seconds |
Certification
|
USA and Canada Safety: UL 61010-1, UL 61010-2-030, CAN/CSA-C22.2 No. 61010-1 EMC: FCC Part 15 subpart B, ICES-003 Radio: FCC Part 15 subpart C, RSS-210, RSS-Gen Europe Safety: EN 61010-1, EN 61010-2-030 (CE) EMC: EN ETSI 301 489-1, 301 489-3, 613 326-1 Radio: EN ETSI 300 220-1, 300 220-2 CB Certification IEC 61010-1, IEC 61010-2-030 by Intertek Testing Services |
Flammability rating of |
UL94 V-0
|
Operating temperature |
-25 – 60° C (-13 – 140o F) |
Operating humidity range
|
5% - 90% non-condensing |
Range of rated environmental conditions
The unit is intended for indoor use.
Altitude up to 2000m
CAT III
Pollution Degree 2
Certified CTs
General notes
- Solid-core or split-core CTs can be used.
- CT’s accuracy class should be 0.5% or better.
- Relay CTs, or CTs with included burden resistors cannot be used.
The following list includes the CTs that were already tested and approved
by Panoramic Power.
Dixsen CTs
- 600A split (model DBP-58)
- 600A non-split rectangular (model MES-62)
- 1000A split (model DBP-58)
- 1000A non-split rectangular (model MES-60)
Veris CTs
- 600A non-split round (BL601)
- 1000A non-split round (BL102)
Magnelab CTs
- 600A split (ICT-2000-600)
- 600A non-split rectangular (CCT-1200-600)
- 1000A split (ICT-2000-1000)
Troubleshooting
If you encounter a problem, first try the following solutions:
Problem |
Solution |
The sensor is not sending measurements
|
Make sure the circuit has current. Make sure that the sensor arrow points in the direction of the load. Make sure that the sensor LED Make sure the sensors are near enough to the Bridge for the Bridge Check the reception LED of the Bridge. |
Maintenance and Servicing
Maintenance is not required. For any issues, please reach out to your Support Provider who can submit a support ticket on your behalf at: https://www.powerradar.energy/support
Support
More support can be obtained at by submitting a support ticket at:
https://www.powerradar.energy/support .